ARTICLE VII. INTERNATIONAL
FUEL GAS CODE
Sec. 8-700.
Adopted; where filed; amendments.
(a) That certain
document known as the "International Fuel Gas Code, 2009 Edition,"
which has been published as a code in book form by the International Code Council,
chapters two through seven and appendix chapters A, B and C inclusive, three
(3) copies with amendments of which are on file in the office of the City Clerk.
(Ord. No. 2011.33,
9-22-11)
Charter
reference—Adoption by reference, § 2.14.
State law reference—Adoption by reference, A.R.S. § 9-801 et seq.
Sec. 303 APPLIANCE
LOCATION.
Section 303.3 is hereby amended as follows:
Section 303.3
Prohibited locations. Appliances
shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets
or surgical room, or in a space that opens only into such rooms or spaces, or any room operating under negative pressure unless the
appliances are listed for that use except where the installation
complies with one of the following:
1. The appliance is a direct-vent appliance installed in
accordance with the conditions of the listing and the manufacturer’s
instructions.
2. Vented room heaters, wall furnaces, vented decorative
appliances, vented gas fireplaces, vented gas fireplace heaters and decorative
appliances for installation in vented solid fuel-burning fireplaces are
installed in rooms that meet the required volume criteria of Section 304.5.
3. A single wall-mounted unvented room heater is
installed in a bathroom and such unvented room heater is equipped as specified
in Section 621.6 and has an input rating not greater than 6,000 Btu/h (1.76
kW). The bathroom shall meet the required volume criteria of Section 304.5.
4. A single wall-mounted unvented room heater is
installed in a bedroom and such unvented room heater is equipped as specified
in Section 621.6 and has an input rating not greater than 10,000 Btu/h (2.93
kW). The bedroom shall meet the required volume criteria of Section 304.5.
5. The appliance is installed in a room or space that
opens only into a bedroom or bathroom, and such room or space is used for no
other purpose and is provided with a solid weather-stripped door equipped with
an approved self-closing device. All combustion air shall be taken directly
from the outdoors in accordance with Section 304.6.
Liquefied
Petroleum (LPG) appliances shall not be installed in an attic, or other
location that would cause ponding or retention of gas.
Section 303.7 is hereby amended as follows:
Section 303.7 Pit locations. Appliances installed in pits or excavations shall not come in
contact with the surrounding soil. The sides of the pit or excavation shall be
held back a minimum of 12 inches (305 mm) from the appliance. Where the depth
exceeds 12 inches (305 mm) below adjoining grade, the walls of the pit or
excavation shall be lined with concrete or masonry. Such concrete or masonry
shall extend a minimum of 4 inches (102 mm) above to adjacent grade and shall
have sufficient lateral load-bearing capacity to resist collapse. The appliance
shall be protected from flooding in an approved manner. Liquefied petroleum
(LPG) appliances shall not be installed in a pit, or other location that would
cause a ponding or retention of gas.
(Ord. No. 2011.33,
9-22-11)
Sec. 304 COMBUSTION,
VENTILATION AND DILUTION AIR.
Section 304.1 is hereby
amended as follows:
Section 304.1 General. Air for combustion, ventilation and dilution of flue gases for appliances
installed in buildings shall be provided by application of one of the methods
prescribed in Sections 304.5 through 304.9. Where the requirements of Section
304.5 are not met, outdoor air shall be introduced in accordance with one of
the methods prescribed in Sections 304.6 through 304.9. For LPG appliances, any duct serving the
lower opening shall be at the floor level and slope to the outdoors without
traps or pockets. Direct-vent appliances, gas appliances of other than Category
I shall be provided with combustion ventilation and dilution air in accordance
with the appliance manufacturer’s instructions.
Section 304.1.1 is
hereby amended as follows:
Section 304.1.1 Prohibited sources. Combustion
air ducts and openings shall not connect appliance enclosures with space in
which the operation of a fan may adversely affect the flow of combustion air.
Combustion air shall not be obtained from an area in which flammable vapors
present a hazard. Fuel-fired appliances shall not obtain combustion air from
any of the following rooms or spaces:
1. Sleeping rooms.
2. Bathrooms.
3. Toilet rooms.
Exception: The
following appliances may be located in sleeping rooms, bathrooms and toilet
rooms:
1.
Appliances
installed in an enclosure in which all combustion air is taken from the
outdoors and the enclosure is equipped with a solid weather-stripped door and
self-closing device.
2. Direct-vent appliances that obtain all combustion air
directly from the outdoors.
Section 304.11 is hereby
amended as follows:
Section 304.11
Combustion air ducts. Combustion air ducts shall comply with all of the
following:
Exception: Within
dwellings units, unobstructed stud and joist spaces shall not be prohibited
from conveying combustion air, provided that not more than one required
fireblock is removed.
Exception: Direct-vent
gas-fired appliances designed for installation in a solid fuel-burning
fireplace where installed in accordance with the manufacturer's instructions.
(Ord. No.
2011.33, 9-22-11)
Sec. 305 INSTALLATION
Section 305.3 is hereby amended as follows:
Section 305.3 Elevation of ignition
source. Equipment and appliances having an ignition source shall be elevated
such that the source of ignition is not less than 18 inches (457 mm) above the
floor in hazardous locations and public garages, private garages, repair
garages, motor fuel-dispensing facilities and parking garages. For the purpose
of this section, rooms or spaces that are not part of the living space of a
dwelling unit and that communicate directly with a private garage through
openings shall be considered to be part of the private garage.
Exceptions:
1. Elevation of the ignition source is not
required for appliances that are listed as flammable vapor resistant and for installation without elevation.
2. Direct-vent appliances that obtain all
combustion air directly from the outdoors.
3. Clothes dryers installed in private
garages.
Section 305.7 is hereby amended as follows:
Section 305.7 Clearances from grade. Equipment and appliances installed at
grade level shall be supported on a level concrete slab or other approved
material extending not less than 3 inches
(76 mm) above finished grade or shall be suspended a minimum of 6 inches (152
mm) above finished grade. Such supports shall be installed in accordance with
the manufacturer's installation instructions.
(Ord. No. 2011.33,
9-22-11)
Sec. 404. PIPING SYSTEM
INSTALLATION.
Section 404.1 is hereby amended as follows:
Section
404.4.1 Underground piping. No
gas piping shall be permitted under asphalt, concrete or other paved surface
that adjoins any building or structure unless installed in a gas-tight conduit
or other approved method of venting is provided.
The conduit shall be of wrought iron, plastic pipe,
steel pipe or other approved conduit material. The conduit shall be protected
from corrosion in accordance with Section 404.9. The interior diameter of the
conduit shall be not less than one-half inch larger than the outside diameter
of the gas pipe within. The conduit shall extend to a point not less than 12
inches (305 mm) beyond or 4 inches (102 mm) above the paved surface. The ends
shall not be sealed.
Section 404.10 is hereby amended as follows:
Section 404.10 Minimum burial depth. Underground piping systems shall be
installed a minimum depth of 12 inches (305 mm) below grade for metal, and 18
inches (457 mm) below grade for plastic piping.
Section 404.10.1 is
hereby deleted.
Section 404.15.1 is hereby amended as follows:
Section 404.15.1 Limitations. Plastic pipe shall be installed outdoors underground
only. Plastic pipe shall not be used within or under any building or slab or be
operated at pressures greater than 100 psig (689 kPa) for natural gas or 30
psig (207 kPa) for LP-gas.
Exceptions:
1.
Plastic
pipe shall be permitted to terminate above ground outside of buildings where
installed in pre-manufactured anodeless risers or service head adapter risers
that are installed in accordance with the manufacturer's installation
instructions.
2.
Plastic
pipe shall be permitted to terminate with a wall head adapter within buildings
where the plastic pipe is inserted in a piping material for fuel gas use in
buildings.
3.
Plastic
pipe shall be permitted under outdoor patio, walkway and driveway slabs
provided that the burial depth complies with Section 404.10 and Section 404.4.1.
(Ord. No. 2011.33, 9-22-11)
Sec. 406 INSPECTION,
TESTING AND PURGING.
Section 406.4 is hereby amended as follows:
Section 406.4 Test pressure measurement. Test pressure shall be measured with a manometer or with a
pressure-measuring device designed and calibrated to read, record, or indicate
a pressure loss caused by leakage during the pressure test period. The source
of pressure shall be isolated before the pressure tests are made.
406.4.1 Test pressure. The test pressure to be used shall be no less than ten (10)
pounds per square inch (69 kPa) gauge pressure, or where approved by the
Building Official, the piping and valves may be tested at a pressure of at
least six (6) inches (152.4 mm) of mercury, measured with a manometer or slope
gauge. For welded piping, and for piping carrying gas at pressures in excess of
fourteen (14) inches (0.4 m) water column pressure, the test pressure shall be
no less than sixty (60) pounds per square inch (413 kPa). Where
the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not
exceed a value that produces a hoop stress in the piping greater than 50 percent
of the specified minimum yield strength of the pipe.
406.4.2 Test duration. Test duration shall be not less than fifteen
(15) minutes or for welded pipe and piping carrying gas at pressures in excess
of fourteen (14) inches (0.4 m) water column pressure, the test duration shall
be not less than thirty (30) minutes. The duration of the test shall not be
required to exceed 24 hours.
406.4.3 Test Gauges. Tests required by this Code which are
performed utilizing dial gauges shall be limited to gauges having the following
pressure increments or graduations:
406.4.3.1. Required pressure tests of ten (10) pounds
(69 kPa) or less shall be performed with gauges having increments of one-tenth
(1/10) pound (0.69 kPa) or less.
406.4.3.2. Required pressure tests exceeding ten (10)
pounds (69 kPa) but less than one hundred (100) pounds (690 kPa) shall be
performed with gauges having increments of one pound (7 kPa) or less.
406.4.3.3. Required pressure tests exceeding one
hundred (100) pounds (690 kPa) shall be performed with gauges having increments
2 psi (14 kPa) or less.
406.4.3.4. Pressure tests required by this code,
which are performed utilizing dial gauges, shall be limited to a gauge having a
maximum gauge rating not exceeding twice the applied test pressure.
(Ord. No. 2011.33,
9-22-11)