ARTICLE VI.  STATE OF ARIZONA PLUMBING CODE

 

Sec. 8-600.  Adopted; where filed; amendments.

 

         (a)     That certain document known as the "Arizona State Plumbing Code," as adopted by the Arizona Uniform Plumbing Code Commission, and which has been published as a code in book form by the International Association of Plumbing and Mechanical Officials, with amendments as published by the Arizona Secretary of State in the Arizona Administrative Code, Title 4, Chapter 48, is hereby adopted as the Plumbing Code of the City of Tempe and made a part of this article, the same as though said code was specifically set forth in full herein.  Three (3) copies of said code shall be filed in the office of the city clerk and kept available for public use and inspection.

 

         (b)     As permitted by Arizona Revised Statutes, §§ 9-805(b) and 41-619, the "International Plumbing Code, 2003 Edition," as published by the International Code Council, three (3) copies with amendments of which are on file in the office of the city clerk, may be used, on an individual project basis as a substitute and variance where deemed appropriate by the building official.  The provisions of this article, other than subsections (a) and (b) of this section, are amendments to the International Plumbing Code as now or hereafter adopted.  All sections in this article, other than subsections (a) and (b) of this section, shall be considered to be both a part of this code and a part of the International Plumbing Code.

(Ord. No. 2005.89, 12-1-05) 

 

            Charter reference—Adoption by reference, § 2.14.

            State law reference—Adoption by reference, A.R.S. § 9-801 et seq.

 

Sec. 201.  General.

 

         Section 201.4 is hereby amended as follows:

 

         201.4.  Terms not defined.  Where terms are not defined through the methods authorized by this chapter, such terms shall have ordinarily accepted meanings such as the context implies. Webster’s Third New International Dictionary of the English Language, Unabridged, shall be considered as providing ordinarily accepted meanings.

(Ord. No. 2005.89, 12-1-05)

 

Sec. 312.  Tests and inspections.

 

         Section 312.1.1 is hereby amended as follows:

 

         312.1.1.  Test gauges.  Gauges used for testing shall be as follows:

 

         1.      Tests requiring a pressure of ten (10) psi (69 kPa) or less shall utilize a testing gauge having increments of 0.10 psi (0.69 kPa) or less.

 

         2.      Tests requiring a pressure of ten (10) psi (69 kPa) but less than or equal to one hundred (100) psi (690 kPa) shall utilize a testing gauge having increments of one psi (7 kPa) or less.

 

         3.      Tests requiring a pressure of greater than one hundred (100) psi (690 kPa) shall utilize a testing gauge having increments of two (2) psi (14 kPa) or less.

 

         Pressure tests required by this code, which are performed utilizing dial gauges, shall be limited to a gauge having a maximum gauge rating not exceeding twice the applied test pressure.

 

         Section 312.5 is hereby amended as follows:

 

         312.5.  Water supply system test.  Upon completion of a section or the entire water supply system, the system or portion completed, shall be tested and proven tight under a water pressure not less than the working pressure of the system; or, for piping systems other than plastic, by an air test of not less than fifty (50) psi (344 kPa).  This pressure shall be held for a test period of at least fifteen (15) minutes.  The water utilized for tests shall be obtained from a potable source of supply.  The required tests shall be performed in accordance with this section.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 313.  Equipment efficiencies.

 

         Section 312.1.1 is hereby repealed.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 504.  Safety devices.

 

         Section 504.6.1 is hereby amended as follows:

 

         Section 504.6.1.  Discharge.  The relief valve shall discharge full size to a safe place of disposal such as, outside the building or an indirect waste receptor.  The discharge pipe shall not have any trapped sections, shall be installed to drain by gravity flow and shall terminate atmospherically not less than six (6) inches (152 mm) nor more than twenty-four (24) inches (610 mm) above the floor or finish grade pointing downward.  The outlet end of the discharge pipe shall not be threaded and such discharge pipe shall not have a valve or tee installed.

 

         Secion 504.7.1 is hereby amended as follows:

 

         504.7.1.  Pan size and drain.  The pan shall not be less than 1.5 inches (38 mm) deep and shall be of sufficient size and shape to receive all dripping or condensate from the tank or water heater. The pan shall be drained by an indirect waste pipe having a minimum diameter of three-fourths (3/4) (19 mm) installed with a uniform alignment at a uniform slope in the direction of discharge of not less than one-eighth (1/8) unit vertical in twelve (12) units’ horizontal (one percent slope).

(Ord. No. 2005.89, 12-1-05) 

 


Sec. 607.  Hot water supply system.

 

         Section 607.2 is hereby amended as follows:

 

         607.2.  Hot water supply temperature maintenance.  Where the developed length of hot water piping from the source of hot water supply to the farthest fixture exceeds one hundred (100) feet (30 480 mm), the hot water supply system may be provided with a method of maintaining the temperature.

 

         Section 607.2.1 is hereby amended as follows:

 

         607.2.1.  Piping insulation.  Circulating hot water system piping may be insulated in accordance with the International Energy Conservation Code.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 608.  Protection of potable water supply. 

 

         Table 608.1 is hereby amended as follows:

 

TABLE 608.1

APPLICATION OF BACKFLOW PREVENTERS

 

 

DEVICE

DEGREE OF HAZARDa

 

APPLICATIONb

 

APPLICABLE STANDARDS

 

Air gap

High or low hazard

Backsiphonage or backpressure

ASME A112.1.2

Air gap fittings for use with plumbing fixtures, appliances and appurtenances

 

High or low hazard

 

Backsiphonage or backpressure

 

ASME A112.1.3

Antisiphon-type fill valves for gravity water closet flush tanks

 

High hazard

 

Backsiphonage only

 

ASSE1002, CSA-B125

 

Barometric loop

High or low hazard

 

 

Backsiphonage only

 

(See Section 608.13.4)

 

Reduced pressure principle

backflow preventer

 

High or low hazard

Backpressure or backsiphonage

Sizes 3/8" – 16"

 

 

ASSE 1013, AWWA C511, CAN/CSA B64.4

Double check backflow

prevention assembly

 

Low hazard

Backpressure or backsiphonage

Sizes 3/8" – 16"

 

ASSE 1015, AWWA C510

Double-check-valve-type

backflow preventer

 

Low hazard

Backpressure or backsiphonage

Sizes ¼" – 1"

 

ASSE 1024

Backflow preventer with

intermediate atmospheric vents

 

Low hazard

Backpressure or backsiphonage

Sizes ¼" – ¾"

 

ASSE 1012, CAN/CSA-B64.3

Backflow preventer for

carbonated beverage machines

 

Low hazard

Backpressure or backsiphonage

Sizes ¼" – 3/8"

 

ASSE 1022

Pipe-applied atmospheric-type vacuum breaker

High or low hazard

Backsiphonage only Sizes ¼" – 4"

ASSE 1001, CAN/CSA-B64.1.1

 


 

Pressure vacuum breaker

assembly

High or low hazard

Backsiphonage only Sizes ½" – 2"

 

ASSE 1020

 

 

Hose-connection vacuum

breaker

 

 

High or low hazard

Low head backpressure or backsiphonage

Sizes ½", ¾", 1"

 

 

 

ASSE 1011, CAN/CSA-B64.2

 

Vacuum breaker wall hydrants, frost-resistant, automatic draining type

 

High or low hazard

Low head backpressure or backsiphonage

Sizes ¾", 1"

 

ASSE 1019, CAN/CSA-B64.2.2

 

Laboratory faucet backflow

preventer

High or low hazard

Low head backpressure and backsiphonage

 

ASSE 1035, CSA B64.7

 

 

Hose connection backflow preventer

 

 

 

High or low hazard

Low head backpressure, rated working pressure backpressure

or backsiphonage

Sizes ½" – 1"

 

 

 

ASSE 1052

 

Spillproof vacuum breaker

High or low

hazard

Backsiphonage only Sizes ¼" – 2"

 

ASSE 1056

 

For SI: 1 inch = 25.4 mm.

a.     Low hazard–See Pollution (Section 202).

        High hazard–See Contamination (Section 202).

b.     See Backpressure (Section 202).

        See Backpressure, low head (Section 202).

        See Backsiphonage (Section 202).

 

         Section 608.16.4 is hereby repealed.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 701.  General.

 

         Section 701.2 is hereby amended as follows:

 

         701.2.  Sewer required.  Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer, where available, or an approved private disposal system in accordance with the Maricopa County Health Department Environmental Service Division.  The public sewer may be considered as not being available only when so determined by the Maricopa County Health Department Environmental Service Division.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 803.  Special wastes.

 

         Section 803.2 is hereby amended as follows:

 

         803.2.  Neutralizing device required for corrosive wastes.  Corrosive liquids, spent acids or other harmful chemicals that destroy or injure a drain, sewer, soil or waste pipe or create noxious or toxic fumes or interfere with sewage treatment processes shall not be discharged into the plumbing system without being thoroughly diluted, neutralized or treated by passing through an approved dilution or neutralizing device.  Such devices shall be automatically provided with sufficient supply of diluting water or neutralizing medium so as to make the contents non-injurious before discharge into the drainage system.  The nature of the corrosive or harmful waste and the method of its treatment or dilution shall be approved prior to installation.  Detailed plans and specifications of the pretreatment facilities may be required by the water utilities manager or designate.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 904.  Vent terminals.

 

         Section 904.1 is hereby amended as follows:

 

         904.1.  Roof extension.  All open vent pipes that extend through a roof shall be terminated at least six (6) inches (152 mm) above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least seven (7) feet (2134 mm) above the roof.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 1003.  Interceptors and separators.

 

         Section 1003.1 is hereby amended as follows:

 

         Section 1003.1.  Where required.  Interceptors and separators shall be provided, when in the judgment of the water utilities manager or designate, to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the building drainage system, the public sewer or sewage treatment plant or processes.

 

         Section 1003.2 is hereby amended as follows:

 

         1003.2.  Approval.  The size, type and location of each interceptor and of each separator shall be approved by the water utilities manager or designate and shall be designed and installed in accordance with the manufacturer’s instructions and the requirements of this section based on the anticipated conditions of use.  Wastes that do not require treatment or separation shall not be discharged into any interceptor or separator.

(Ord. No. 2005.89, 12-1-05) 

 

Sec. 1106.  Size of conductors, leaders and storm drains.

 

         Section 1106.1 is hereby amended as follows:

 

         1106.1.  General.  The size of vertical conductors and leaders, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on an hourly rainfall rate of three (3) inches per hour.

(Ord. No. 2005.89, 12-1-05) 

 


Sec. 1107.  Secondary (emergency) roof drains.

 

         Section 1107.2 is hereby amended as follows:

 

         1107.2.  Separate systems required.  Secondary roof drain systems shall have the end point of discharge separate from the primary system.  Discharge shall be above grade, in a location which would normally be observed by the building occupants or maintenance personnel.

 

                  EXCEPTION:  Secondary drains may be connected to the primary drain system at a point  not less than ten (10) feet (3048 mm) below the secondary drain inlet height when the primary system is designed for a six (6) inch per hour rainfall.

 

         Section 1107.3 is hereby amended as follows:

 

         1107.3.  Sizing of secondary drains.  Where roof drains are required, secondary drains having the same size as the roof drains shall be installed with the inlet flow line located two (2)  inches (51 mm) above the low point of the roof, or overflow scuppers having three (3) times the size of the roof drains may be installed in the adjacent parapet walls.  Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7, and the requirements of the International Building Code, Sections 1608.3.4 and 1608.3.5.  Scuppers shall not have an opening dimension of less than four (4) inches (102 mm).  The flow through the primary system shall not be considered when sizing the secondary roof drain system.

(Ord. No. 2005.89, 12-1-05)