ARTICLE VI. INTERNATIONAL
PLUMBING CODE
Sec. 8-600.
Adopted; where filed; amendments.
(a) That certain
document known as the "International Plumbing Code, 2009 Edition"
which has been published as a code in book form by the International Code
Council, chapters two through fifteen and appendix chapters C and E inclusive,
three (3) copies with amendments of which are on file in the office of the City
Clerk.
(Ord. No. 2011.33,
9-22-11)
Charter
reference—Adoption by reference, § 2.14.
State law reference—Adoption by reference, A.R.S. § 9-801 et seq.
Sec. 312 TESTS AND
INSPECTIONS.
Section 312.1.1
is hereby amended as follows:
Section
312.1.1 Test gauges. Gauges
used for testing shall be as follows:
1. Tests requiring a pressure of 10 psi (69 kPa)
or less shall utilize a testing gauge having increments of 0.10 psi (0.69 kPa)
or less.
2. Tests requiring a pressure of greater than 10
psi (69 kPa) but less than or equal to 100 psi (689 kPa) shall utilize a
testing gauge having increments of 1 psi (6.9 kPa) or less.
3. Tests requiring a pressure of greater than
100 psi (689 kPa) shall utilize a testing gauge having increments of 2 psi (14
kPa) or less.
Pressure tests required by this code,
which are performed utilizing dial gauges, shall be limited to a gauge having a
maximum gauge rating not exceeding twice the applied test pressure.
(Ord. No. 2011.33,
9-22-11)
Sec. 403 Minimum
Plumbing Facilities.
Section 403.1 is hereby amended as follows:
Section 403.1 Minimum
number of fixtures. The minimum number of plumbing fixtures shall be
determined by the International Building
Code.
(Ord. No. 2011.33,
9-22-11)
Sec. 504 SAFETY
DEVICES.
Section 504.6 is hereby
amended as follows:
Section 504.6
Requirements for discharge piping. The
discharge piping serving a pressure relief valve, temperature relief valve or
combination thereof shall:
1.
Not be directly
connected to the drainage system.
2.
Discharge in a
downward direction.
3.
Not be smaller
than the diameter of the outlet of the valve served and shall discharge full
size to the air gap.
4.
Serve a single
relief device and shall not connect to piping serving any other relief device
or equipment.
5.
Discharge through
an air gap to the floor, to the pan serving the water heater or storage tank,
to a waste receptor or to the outdoors.
6.
Discharge in a
manner that does not cause personal injury or structural damage.
7.
Discharge to a
termination point that is readily observable by the building occupants.
8.
Not be trapped.
9.
Be installed to
flow by gravity.
10.
Terminate not
less than 6 inches (152 mm) and not more than 12 inches (610 mm) above finished
grade, the floor or waste receptor.
11.
Not have a
threaded connection at the end of the piping.
12.
Not
have valves or tee fittings.
13.
Be
constructed of those materials listed in Section P2904.5 or materials tested,
rated and approved for such use in accordance with ASME A112.4.1.
Section 504.7.1 is hereby
amended as follows:
Section 504.7.1 Pan size and drain. The pan shall not be less than 1.5 inches (38 mm) deep
and shall be of sufficient size and shape to receive all dripping or condensate
from the tank or water heater. The pan shall be drained by an indirect waste
pipe having a minimum diameter of ¾ inch (19 mm) installed with a uniform
alignment at a uniform slope in the direction of discharge of not less than
one-eighth unit vertical in 12 units’ horizontal (1-percent slope). Piping for
safety pan drains shall be of those materials listed in Table 605.4.
(Ord. No. 2011.33,
9-22-11)
Sec. 604 DESIGN
OF BUILDING WATER DISTRIBUTION SYSTEM
Section 604.1 is hereby
amended as follows:
Section 604.1 General. The design of the water distribution system shall be
determined according to the methods in Appendix E or when approved by the code
official, to design methods conforming to acceptable engineering practice.
(Ord. No. 2011.33,
9-22-11)
Sec 701 GENERAL.
Section 701.2 is hereby amended as follows:
Section 701.2
Sewer required. Every building in
which plumbing fixtures are installed and all premises having drainage piping
shall be connected to a public sewer, where available, or an approved private
disposal system in accordance with the Maricopa County Health Department
Environmental Service Division. The public sewer may be considered as not being
available only when so determined by the Maricopa County Health Department
Environmental Service Division.
(Ord. No. 2011.33,
9-22-11)
Sec. 803 SPECIAL WASTES.
Section 803.2 is hereby
amended as follows:
Section 803.2
Neutralizing device required for corrosive wastes. Corrosive liquids, spent acids or other harmful chemicals that
destroy or injure a drain, sewer, soil or waste pipe or create noxious or toxic
fumes or interfere with sewage treatment processes shall not be discharged into
the plumbing system without being thoroughly diluted, neutralized or treated by
passing through an approved dilution or neutralizing device. Such devices shall
be automatically provided with sufficient supply of diluting water or
neutralizing medium so as to make the contents non-injurious before discharge
into the drainage system. The nature of the corrosive or harmful waste and the
method of its treatment or dilution shall be approved prior to installation. Detailed
plans and specifications of the pretreatment facilities may be required by the
Water Utilities Manager or designate.
(Ord. No. 2011.33,
9-22-11)
Sec. 904 VENT
TERMINALS.
Section 904.1 is hereby
amended as follows:
Section 904.1 Roof extension. All open vent pipes that extend through a
roof shall be terminated at least 6 inches (152 mm) above the roof, except that
where a roof is to be used for any purpose other than weather protection, the
vent extensions shall be run at least 7 feet (2134 mm) above the roof.
(Ord. No. 2011.33,
9-22-11)
Sec. 1003
INTERCEPTORS AND SEPARATORS.
Section 1003.1 is hereby
amended as follows:
Section 1003.1
Where required. Interceptors and
separators shall be provided, when required by the Water Utilities Manager, to
prevent the discharge of oil, grease, sand and other substances harmful or
hazardous to the building drainage system, the public sewer or sewage treatment
plant or processes.
Section 1003.2 is hereby
amended as follows:
Section 1003.2
Approval. The size, type and location of
each interceptor and of each separator shall be approved by the Water Utilities
Manager and shall be designed and installed in accordance with the
manufacturer’s instructions and the requirements of this section based on the
anticipated conditions of use. Wastes that do not require treatment or
separation shall not be discharged into any interceptor or separator.
Section 1003.3.4 is hereby
amended as follows:
Section
1003.3.4 Grease interceptors and automatic grease removal devices. Grease
interceptors and automatic grease removal devices shall be sized by the Water
Utilities Manager. Grease interceptors and automatic grease removal devices
shall be approved by the Water Utilities Manager. Grease interceptors and
automatic grease removal devices shall be installed in accordance with the
manufacturer’s instructions.
(Ord. No. 2011.33,
9-22-11)
Sec. 1106 SIZE OF CONDUCTORS, LEADERS, SCUPPERS AND STORM DRAINS.
Section 1106.1 is hereby
amended as follows:
Section 1106.1 General. The size of vertical conductors and leaders, building storm drains,
building storm sewers, and any horizontal branches of such drains or sewers
shall be based on an hourly rainfall rate of 3" per hour.
Section 1106.3 is hereby
amended as follows:
Section
1106.3 Building storm drains, sewers and scuppers. The size of the building storm drain, building storm sewer and
their horizontal branches having a slope of one-half unit or less vertical in
12 units horizontal (4-percent slope) shall be based on the maximum projected
roof area in accordance with Table 1106.3. The minimum slope of horizontal
branches shall be one-eighth unit vertical in 12-units horizontal (1-percent
slope) unless otherwise approved.
Scuppers shall have a minimum vertical dimension of 6 inches
(152 mm) and a minimum width of 1/2 inch (12.7 mm) per 100 square feet (9.29
m²) of tributary area, but not less than 6 inches (152 mm).
Where downspouts are used,
an overflow opening equal in size and shape to the roof scupper shall be
provided in the downspout, with the bottom of the opening located between 0 and
2 inches (51 mm) above the bottom of the roof scupper.
(Ord. No. 2011.33,
9-22-11)
Sec. 1107 SECONDARY (EMERGENCY) ROOF DRAINS.
Section 1107.2 is hereby
amended as follows:
Section
1107.2 Separate systems required. Secondary roof drain systems shall have the end point
of discharge separate from the primary system. Discharge shall be above grade,
in a location which would normally be observed by the building occupants or
maintenance personnel.
Exception: Secondary drains may be connected to the primary
drain system at a point not less than 10' (3048 mm) below the secondary drain
inlet height when the primary system is designed for a 6" per hour
rainfall.
Section 1107.3 is hereby
amended as follows:
Section 1107.3
Sizing of secondary drains. Secondary (emergency) roof drainage systems shall be
sized in accordance with Section 1106 based on the rainfall rate for which the
primary system is sized in Tables 1106.2(1), 1106.2(2), 1106.3 and 1106.6. Secondary
roof drains shall be installed with their inlet flow line located 2 inches (51
mm) above the low point of the roof. In lieu of secondary roof drains, overflow
scuppers having three times the size of the roof drains may be installed in the
adjacent parapet walls. Secondary scuppers shall be sized to prevent the depth
of ponding water from exceeding that for which the roof was designed as
determined by Section 1101.7, and the requirements of the International
Building Code, Sections 1611.1 and 1611.2. Scuppers shall not have an opening
dimension of less than 6 inches (102 mm). The flow through the primary system
shall not be considered when sizing the secondary drainage system.
(Ord. No. 2011.33,
9-22-11)