ARTICLE IX. INTERNATIONAL ENERGY CONSERVATION CODE
Sec. 8-900. Adopted; where filed; amendments.
(a) That certain document known as the
"International Energy Conservation Code, 2009 Edition," which has
been published as a code in book form by the International Code Council,
chapters two through six, three (3) copies with amendments of which are on file
in the office of the City Clerk.
(Ord. No. 2011.33, 9-22-11)
Charter reference—Adoption by
reference, § 2.14.
State law reference—Adoption by reference, A.R.S. § 9-801 et seq.
Sec. 401 GENERAL.
Section 401.1 is hereby
amended as follows:
401.1 Scope. This chapter applies to
residential buildings.
Exception: Evaporative
coolers are not covered by this code.
Section 401.2 is hereby
amended as follows:
Section
401.2 Compliance.
Projects shall comply with Sections 401, 402.4, 402.5, and 403.1,
403.2.2, 403.2.3, and 403.3 through 403.9 (referred to as the mandatory
provisions) and either:
1. Sections 402.1 through 402.3,
403.2.1 and 404.1 (prescriptive); or
2.
Section 405 (performance).
As an
alternative, additions, alterations, remodels, and repairs may comply with the
department’s standard energy conservation details.
(Ord. No. 2011.33, 9-22-11)
Sec. 402 BUILDING THERMAL
ENVELOPE
Section 402.2.4.1 is
hereby amended as follows:
Section 402.2.4.1 Insulation for Masonry Mass walls. Exterior or Fire Walls shall not use absorbent (open
cell and water-reactive, supporting mold growth) organic insulation at the
exterior, integral between wythes, or integral within otherwise unfilled grout
spaces such as within cores or cells of Concrete Masonry, Clay, or Shale
Masonry Units. To maintain the required R-Values and U-Factors, closed cell
insulation (non-absorbent) such as, though not limited to, closed-cell
polyurethane foamed-in-place as well as closed cell expanded, extruded, or
sprayed polystyrenes, gas-impermeable faced polyisocyanurates, adsorbent,
non-water reactive, non-mold supporting insulation, and inorganic types are
acceptable.
Section 402.2.4.2 is
hereby amended as follows:
Section 402.2.4.2 Drainage of Masonry. If an exterior post-applied film-forming coating and/or sealant (paints,
block-fillers, parges, breathable film-formers, etc.) is used on exposed
masonry then flashings and weeps shall drain to the exterior as designed.
Section 402.2.4.3 is
hereby amended as follows:
Section
402.2.4.3 Moisture Resistance of Masonry. All exterior exposed-face Concrete Masonry Units
(CMU) which have Integral Water Repellent (IWR) shall
comply with National Concrete Masonry Association (NCMA) standards and tests
(NCMA CMU WR1, WR2, or WR3) for moisture resistance. Exposed mortar shall have
Integral Water Repellent (IWR).
If post-applied coatings and / or sealants are used,
they shall give evidence of moisture resistance so as to maintain thermal
efficiency of the masonry wall assembly.
When
moisture resistance is demonstrated the related tests or demonstrations need to
be performed before interior finishes are in place.
(Ord. No. 2011.33, 9-22-11)
Sec. 403 SYSTEMS (Mandatory)
Section 403.2.1 is hereby
amended as follows:
Section
403.2.1 Insulation. Supply ducts shall be insulated
to a minimum of R-8. All other ducts shall be insulated to a minimum of R-6.
Exceptions:
1.
Ducts
or portions thereof located completely inside the building thermal envelope.
2.
Supply
and return ducts may be insulated to a minimum of R-6 when one or more of the
following conditions are met:
·
Minimum
seer rating of space heating/cooling system is 14.
·
Maximum
U-factor is 0.64 and maximum SHGC is 0.35 for all fenestration products.
·
Wall
insulation minimum R-value is R-19.
·
Residential
buildings that meet the requirements of a national,
state or local energy efficiency program to exceed the energy efficiency
required by this code. Buildings approved in writing by such an energy
efficiency program shall be considered in compliance with this code. The
requirements identified as "mandatory" in Chapters 4 and 5 of this
code, as applicable, shall be met.
·
Residential
buildings that meet the requirements of Section 404.
(Ord.
No. 2011.33, 9-22-11)
Section
501 GENERAL
Section 501.1 is hereby
amended as follows:
Section 501.1 Scope. The
requirements contained in this chapter are applicable to commercial buildings,
or portions of commercial buildings. These commercial buildings shall meet
either the requirements of ASHRAE/IESNA Standard 90.1, Energy Standard for
Buildings Except for Low-Rise Residential Buildings, or the requirements
contained in this chapter.
Exceptions:
1. Lighting
and their controls, that are required by the City of Tempe,
Zoning and Development Code, are not regulated by this code.
2. Evaporative
coolers are not covered by this code.
(Ord.
No. 2011.33, 9-22-11)
Section
502 BUILDING ENVELOPE REQUIREMENTS
Section 502.2.3.1 is
hereby amended as follows:
Section 502.2.3.1 Insulation for Masonry
Mass walls. Exterior or Fire Walls shall not
use absorbent (open cell and water-reactive, supporting mold growth) organic
insulation at the exterior, integral between wythes, or integral within
otherwise unfilled grout spaces such as within cores or cells of Concrete
Masonry, Clay, or Shale Masonry Units. To maintain the required R-Values and
U-Factors, closed cell insulation (non-absorbent) such as, though not limited
to, closed-cell polyurethane foamed-in-place as well as closed cell expanded,
extruded, or sprayed polystyrenes, gas-impermeable faced polyisocyanurates,
adsorbent, non-water reactive, non-mold supporting insulation, and inorganic
types are acceptable.
Section 502.2.3.2 is
hereby amended as follows:
Section 502.2.3.2 Drainage of Masonry. If an exterior post-applied
film-forming coating and/or sealant (paints, block-fillers, parges, breathable
film-formers, etc.) is used on exposed masonry then flashings and weeps shall
drain to the exterior as designed.
Section 502.2.3.3 is
hereby amended as follows:
Section
502.2.3.3. Moisture Resistance of Masonry. All
exterior exposed-face Concrete Masonry Units (CMU) which have
Integral Water Repellent (IWR) shall comply with National Concrete Masonry
Association (NCMA) standards and tests (NCMA CMU WR1, WR2, or WR3) for moisture
resistance. Exposed mortar shall have Integral Water Repellent (IWR).
If
post-applied coatings and / or sealants are used, they shall give evidence of
moisture resistance so as to maintain thermal efficiency of the masonry wall
assembly.
When
moisture resistance is demonstrated the related tests or demonstrations need to
be performed before interior finishes are in place.
(Ord.
No. 2011.33, 9-22-11)